Evocyl Calorifier

Evocyl Calorifier

Evocyl calorifier for large volumes of hot water storage.

For systems requiring large volumes of hot water storage, a number of ThermaQ calorifier models are available. The Evocyl range of calorifiers are manufactured from high grade stainless steel with coil sizes to suit all applications.

Supplied with money saving and highly accurate digital thermostat. This unique thermostat also has a built in anti-Legionella function.

Specification


  • 5 year cylinder warranty and 2 years parts warranty.
  • Sizes 350L to 1000L in 690mm diameter.
  • Cylinder manufactured from high grade Duplex Stainless Steel.
  • Totally insulated with 50mm 100% CFC and HCFC free polyurethane to minimise heat loss.
  • 22mm threaded coil connections. 1” bsp female cold feed, hot flow, secondary return, and de-stratification connections.
  • Flat base for stability.
  • Supplied with high quality unvented installation components.
  • All plumbing connections are clearly identified and accessible at the front of the cylinder.
  • Efficient primary coil.
  • Direct Units supplied fitted with Titanium immersion heaters as standard. Indirect supplied with incoloy immersions fitted as standard.
  • Supplied with all safety controls as  required by UK Building Regulations and Water Regulations.
Code TQDIR
0400
TQDIR
0500
TQDIR
0600
Capacity (L) 370 460 560
Height 1520 1850 2220
Diameter 690 690 690
Immersion Heater 1 300 300 300
Immersion Heater 2 650 850 1050
Immersion Heater 3 1125 1450 1825
Upper Destratification Tapping 1125 1450 1825
Secondary Return 1230 1550 1925
T&P Valve 1250 1570 1945
Code TQIND
0400
TQIND
0500
TQIND
0600
Capacity (L) 365 455 555
Height 1520(J) 1850(J) 2220(J)
Diameter 690 690 690
Cold Inlet 492(A) 492(A) 492(A)
Boiler Coil 392(B) 392(B) 392(B)
Stat Pocket 400(C) 400(C) 400(C)
Immersion Heater 1 432(D) 432(D) 432(D)
Lower Destratification Tapping 260(E) 260(E) 260(E)
Upper Destratification Tapping 960(F) 1075(F) 1250(F)
Immersion Heater 2 910(G) 985(G) 1160(G)
Secondary Return 1240(H) 1560(H) 1860(H)
T&P Valve 1260(I) 1590(I) 1880(I)
Product Weight
Empty
(KG)
Weight
Full
(KG)
Full Cold
Capacity
(Litres)
Reheat Indirect*
(Minutes)
Reheat 3KW
Immersion**
(Minutes)
Heat
Exchange***
(kW)

Dedicated
Solar
(Litres)
Standing
Loss
Cylinder
(kWh/24h)
Standing
Loss
Cylinder
(Watts)
ERP
Energy
Rating
ERP
Load
Profile
ERP
Energy
Efficiency
ηwh%
Annual
Energy
Usage
kWh/Year
Evocyl 400
Direct
74 444.00 370.00 - 345 - - 1.86 78 D XL 37 4596
Evocyl 400
Indirect
76 441.55 365.55 45 307 17.62 0 1.86 78 C - - -
Evocyl 400
Direct Solar
76 441.55 365.55 45 272 17.62 213 1.86 78 C - - -
Evocyl 400
Solar Twin
78 439.10 361.10 45 142 18.97/17.62 161 1.86 78 C - - -
Evocyl 500
Direct
90 550.00 460.00 - 446 - - 2.20 92 D XXL 37 5870
Evocyl 500
Indirect
92 547.55 455.55 56 408 20.11 - 2.20 92 C - - -
Evocyl 500
Direct Solar
82 547.55 455.55 56 362 20.11 266 2.20 92 C - - -
Evocyl 500
Solar Twin
94 545.10 451.10 56 220 22.05/20.11 201 2.20 92 C - - -
Evocyl 600
Direct
101 661.00 560.00 - 583 - - 2.42 101 D XXL 37 5918
Evocyl 600
Indirect
103 658.55 555.55 68 525 20.57 - 2.42 101 C - - -
Evocyl 600
Direct Solar
103 658.55 555.55 68 436 20.57 320 2.42 101 C - - -
Evocyl 600
Solar Twin
104 656.10 551.10 68 298 23.17/20.57 242 2.42 101 C - - -

Test